Chiller J-50 - source of cold water, air cooled
The J-50 chiller is a compact chiller for indoor environment. It contains a cooling circuit with appropriate protections, one semi-hermetic compressor, air cooled condenser with fans, regulation, water tank with evaporator, pump with bypass, electrical switchboard, digital temperature controller, fault showing. The chiller heats the ambient air, in lower spaces it is necessary to vent the heated air through the discharge air duct. In the winter months, the chiller can heat space. If the room is air-conditioned at the working place of the chiller, in the summer months we recommend sucking the air through the suction duct from outside.
TECHNICAL PARAMETERS | ||
Cooling capacity: | 50 kW at water temperature 13 °C | |
Input power: | 16.7 kW | |
Current: | 46.0 A | |
Starting current: | 96.0 A | |
Voltage: | 3+N+PE~50Hz 400/230V TN-S | |
Circuit breaker: | motor circuit breaker 50 A |
|
Supply cable: | CYKY-J 5x10 | |
Refrigerant / volume: | R 407C / 16.0 kg |
|
Tank volume: | 500 l | |
Liquid flow / pressure | 150 l/min / 3.0 bar | |
Air flow: | 14,000 m3/h | |
Weight: | 770 kg |
|
Coverage: | IP 43 |
Flow of used pumps: | Cooling capacity: |
Heating capacity: |